Brand Name : GFUVE
Model Number : TEST-330B
Certification : CE/ISO9001, CNAS, EPRI, KEMA
Place of Origin : Beijing, China (Mainland)
MOQ : 1SET
Price : FOB USD25000-35000 / set
Payment Terms : T/T Western Union
Supply Ability : 100Set/month
Delivery Time : 15days
Packaging Details : Aluminium alloy case
CLASS : 0.1
LCD : 8.4 TFT LCD
Keyword : three phase protective relay test system
Function : 3 phase current and 5 phase voltage output
Frequency : 0-1050Hz
Weight : 16.6KG
Current output : max 90A
Voltage output : max 300V
TEST-330B Portable Three phase secondary current injection protective relay test system for distance protection
Test-330 Portable Three phase protective relay test system s a three phase current output and five phase voltage output relay tester with embedded host machine equipped with Complex Programmable Logic Device. It can test all kinds of relay and protection device, for example differential protection and distance protections.
AC current output | Phase current output (effective value) | 3×0-30A |
Maximum output power | 260VA/phase | |
Maximum parallel current output (effective value) | 0-90A | |
Long-term allowable working value of phase current (effective value) | >10A | |
Allowable working time of maximum current | >11s | |
Accuracy | <±0.2% | |
AC voltage output | Phase voltage output (effective value) | 5×0-130V |
Line voltage output (effective value) | 0-260V | |
Maximum output power | 70VA/phase | |
Accuracy | <±0.2% | |
DC voltage output | Output range | 0-300V or 5×0- ±130V |
Maximum output power | 130VA | |
Accuracy | <±0.2% | |
DC current output | Output range | -10-10A or 3×0- ± 10A |
Maximum output power | 200VA | |
Accuracy | <±0.2% | |
Binary input | Idle contact | 1-20mA, 24V (DC) |
Electric potential contact | 0-250V (DC) | |
Binary output | Idle contact | 250V/0.5A (DC) |
Rated output | Frequency error | <±0.01Hz |
Phase error | <±0. 2° | |
Waveform distortion | <±0.3% (fundamental wave) | |
Time error | <40µs | |
Output frequency | 0-1050Hz | |
Superposed harmonic wave | 0-21times | |
Power voltage | Allowable range | AC220V±10%, 50/60Hz±10% |
Ambient temperature | Use range | 0-45℃ |
Storage range | -25-70℃ | |
Time measurement | Test range | 0.1ms-999999.999s |
Exterior appearance of cabinet | Imported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected. Dimension of cabinet(L x W x H): 360mm ×195mm ×375mm | |
Weight of cabinet | Weight of host machine | 16.6kg |
Load-bearing output | Selectable between light load or heavy load output (When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode) |